The structural design of the dry-type transformer with second-level energy efficiency is advanced, and high-temperature insulation materials that are resistant to both sound and visual influence are adopted. It has the characteristics of good no-load energy consumption, safety and reliability, etc., ensuring a stable power output.
It is mainly used for the wiring of electrical circuits, electrical equipment and electromechanical equipment, providing stable power output quality for the power matching of various electrical and mechanical equipment.
It has a high insulation class and stable and reliable performance. In practical applications, it can provide continuous and stable high-quality voltage transformation services.
It has high working efficiency and can provide efficient power output to ensure the safe operation of the power supply.
It has good heat dissipation performance and excellent performance reliability during long-term operation.
Standartlarni amalga oshirish
GB 1094-2013 《Power transformer》
GB/T 2900.95 Electrical terms transformers, voltage regulator and reactors
GB/T 10228 Technical parameters and requirements of dry type powertransformers
GB 20052-2020 Power transformer energy efficiency limit value and energy
IEC 60076 《Power transformer》
Tur tavsifi
Oddiy xizmat ko'rsatish holati
1000 metr balandlikda
Atrof-muhitning eng yuqori harorati +40 daraja Selsiy
Eng yuqori kunlik o'rtacha harorat +20 daraja Selsiy
Eng past tashqi havo harorati -20 daraja Selsiy
Ishlash parametrlari
Nominal quvvat (kVA) | Electrical steel belt | Amorf qotishma | Short-circuitimpedence(%) | ||||||
Yuksiz yo'qotish (Vt) | Yukning yo'qolishi (Vt) | Yuksiz yo'qotish (Vt) | Yukning yo'qolishi (Vt) | ||||||
B (100℃) | F(120℃) | H(145℃) | B(100℃) | F(120℃) | H(145℃) | ||||
30 | 130 | 605 | 640 | 685 | 60 | 605 | 640 | 685 | 4.0 |
50 | 185 | 845 | 900 | 965 | 75 | 845 | 900 | 965 | |
80 | 250 | 1160 | 1240 | 1330 | 100 | 1160 | 1240 | 1330 | |
100 | 270 | 1330 | 1415 | 1520 | 110 | 1330 | 1415 | 1520 | |
125 | 320 | 1565 | 1665 | 1780 | 130 | 1565 | 1665 | 1780 | |
160 | 365 | 1800 | 1915 | 2050 | 145 | 1800 | 1915 | 2050 | |
200 | 420 | 2135 | 2275 | 2440 | 170 | 2135 | 2275 | 2440 | |
250 | 490 | 2330 | 2485 | 2665 | 195 | 2330 | 2485 | 2665 | |
315 | 600 | 2945 | 3125 | 3355 | 235 | 2945 | 3125 | 3355 | |
400 | 665 | 3375 | 3590 | 3850 | 265 | 3375 | 3590 | 3850 | |
500 | 790 | 4130 | 4390 | 4705 | 305 | 4130 | 4390 | 4705 | |
630 | 910 | 4975 | 5290 | 5660 | 360 | 4975 | 5290 | 5660 | |
630 | 885 | 5050 | 5365 | 5760 | 350 | 5050 | 5365 | 5760 | 6.0 |
800 | 1035 | 5895 | 6265 | 6715 | 410 | 5895 | 6265 | 6715 | |
1000 | 1205 | 6885 | 7315 | 7885 | 470 | 6885 | 7315 | 7885 | |
1250 | 1420 | 8190 | 8720 | 9335 | 550 | 8190 | 8720 | 9335 | |
1600 | 1665 | 9945 | 10555 | 11320 | 645 | 9945 | 10555 | 11320 | |
2000 | 2075 | 12240 | 13005 | 14005 | 850 | 12240 | 13005 | 14005 | |
2500 | 2450 | 14535 | 15445 | 16605 | 1020 | 14535 | 15445 | 16605 |