BH-0.66 1-shakl joriy transformatori ichki foydalanish uchun mo'ljallangan. Bu, maksimal tashqi voltaj 0.72KV va undan past, yuk quvvati faktori 0.8 va nomerli chastota 50Hz bo'lgan almashuvli joriy shakli elektr energiyasini o'lchash yoki hisoblash uchun ishlatiladi. U busbar yoki asos pleyt orqali sabablantirilgan. Joriy transformatorining o'rtasida bir dona busbar yoki kabel o'tishi mumkin bo'lgan oyna mavjud.
Standartlarni bajarish
GB⁄T 20840«Transformer»
IEC 61869«Ijroiy transformatorlar»
Turi ta'rifi
Oddiy ish sharoiti
Eng yuqori balandlik 1000m dan oshmaydi.
Joriy transformator ishlatish uchun muhit harorati: uy ichida -5℃ dan 40℃ gacha.
Joriy transformator uy ichida ishlatiladi va boshqa ko'rsatilgan ish shartlari quyidagilar:
a) Qo'shimcha sur'katcha radiatsiyasining ta'siri e'tiborsiz qilib olinishi mumkin.
b) Yuqori havo ayrimi, qatorli tozalikka ega emas, tozalikka, yong'ina, korroziv gazlarga, bukmalarga yoki tuzlarga ega emas.
c) Namlik shartlari quyidagicha:
1) 24 soat ichida o'lchangan nisbiy namlikning o'rtacha qiymati 95% dan oshmaydi.
2) 24 soat ichida suv bukmasining bosimining o'rtacha qiymati 2.2kPa dan oshmaydi.
3) Bir oy ichida nisbiy namlikning o'rtacha qiymati 90% dan oshmaydi.
4) Bir oy ichida suv bukmasining bosimining o'rtacha qiymati 1.8kPa dan oshmaydi.
Ишлаб чиқариш параметри
Model raqami | Joriy nisbat A | Nominal chiqish VA | Yurak orqali burilgan turnlar soni | ||||
1-bazi | 0.5 darajasi | 0.5S daraja | 0.2 daraja | 0.2S daraja | |||
80 I | 300/5 | 5 | 5 | 2.5 | 2.5 | 2.5 | 1 |
400/5 | 5 | 5 | 2.5 | 2.5 | 2.5 | 1 | |
500/5 | 10 | 10 | 5 | 5 | 5 | 1 | |
600/5 | 10 | 10 | 5 | 5 | 5 | 1 | |
750/5 | 10 | 10 | 10 | 10 | 5 | 1 | |
800/5 | 10 | 10 | 10 | 10 | 5 | 1 | |
1000/5 | 10 | 10 | 10 | 10 | 5 | 1 | |
1200/5 | 20 | 20 | 20 | 20 | 5 | 1 | |
1500/5 | 20 | 20 | 20 | 20 | 10 | 1 | |
2000/5 | . | * | 20 | 20 | 10 | 1 | |
2500⁄5 | . | * | 30 | 30 | 10 | 1 | |
2000/5 | 20 | 20 | . | - | . | 1 | |
2500⁄5 | 30 | 30 | - | * | . | 1 | |
300/1 | 5 | 5 | 1 | ||||
400/1 | 5 | 5 | 5 | 5 | 1 | ||
500/1 | 10 | 10 | 5 | 5 | 5 | 1 | |
600/1 | 10 | 10 | 5 | 5 | 5 | 1 | |
750/1 | 10 | 10 | 10 | 10 | 5 | 1 | |
800/1 | 10 | 10 | 10 | 10 | 5 | 1 | |
1000/1 | 10 | 10 | 10 | 10 | 5 | 1 | |
1200/1 | 20 | 20 | 20 | 20 | 5 | 1 | |
1500/1 | 20 | 20 | 20 | 20 | 10 | 1 | |
2000/1 | 20 | 20 | 20 | 20 | 10 | 1 | |
2500⁄1 | 30 | 30 | 30 | 30 | 10 | 1 | |
20 I | 75/5100/5 | 2.52.5 | 11 | ||||
30/5 | 5 | 2.5 | 2.5 | 2.5 | 2.5 | 5 | |
30 I | 50/5 | 5 | 2.5 | 2.5 | 2.5 | 2.5 | 3 |
75/5 | 5 | 2.5 | 2.5 | 2.5 | 2.5 | 2 | |
75/5 | 2.5 | 1 | |||||
100/5 | 2.5 | 1 | 1 | ||||
100/5 | 5 | 5 | 2.5 | 2.5 | 2.5 | 2 | |
150/5 | 5 | 2.5 | 2.5 | 2.5 | 2.5 | 1 | |
200/5 | 5 | 5 | 2.5 | 2.5 | 2.5 | 1 | |
250/5 | 5 | 5 | 2.5 | 2.5 | 2.5 | 1 | |
300/5 | 5 | 5 | 2.5 | 2.5 | 2.5 | 1 | |
400/5 | 5 | 5 | 2.5 | 2.5 | 2.5 | 1 | |
500/5 | 5 | 5 | 1 | ||||
600/5 | 10 | 10 | 1 | ||||
30/1 | 2.5 | 2.5 | 5 | ||||
50/1 | 2.5 | 2.5 | 3 | ||||
75/1 | 1 | 12 | |||||
75/1 | 2.5 | 2.5 | |||||
100/1 | 2.5 | 1 | 1 | ||||
100/1 | 5 | 5 | 2 | ||||
150/1 | 2.5 | 2.5 | 11 | ||||
200/1 | 5 | 5 | |||||
250/1 | 5 | 5 | 11 | ||||
300/1 | 5 | 5 | |||||
100 I | 600/5 | 10 | 10 | 5 | 5 | 5 | 1 |
750/5 | 10 | 10 | 10 | 10 | 5 | 1 | |
800/5 | 10 | 10 | 10 | 10 | 5 | 1 | |
1000/5 | 10 | 10 | 10 | 10 | 5 | 1 | |
1200/5 | 20 | 20 | 20 | 20 | 5 | 1 | |
1500/5 | 20 | 20 | 20 | 20 | 10 | 1 | |
2000/5 | 20 | 20 | 20 | 20 | 10 | 1 | |
2500⁄5 | . | . | 30 | 30 | 10 | 1 | |
3000⁄5 | . | . | 30 | 30 | 10 | 1 | |
2500⁄5 | 30 | 30 | * | * | * | 1 | |
3000⁄5 | 30 | 30 | . | * | * | 1 | |
600/1 | 10 | 10 | 5 | 5 | 5 | 1 | |
750/1 | 10 | 10 | 10 | 1 | |||
800/1 | 10 | 10 | 10 | 10 | 5 | 1 | |
1000/1 | 10 | 10 | 10 | 10 | 5 | 1 | |
1200/1 | 20 | 20 | 20 | 20 | 5 | 1 | |
1500/1 | 20 | 20 | 20 | 20 | 10 | 1 | |
2000/1 | 20 | 20 | 20 | 10 | 1 | ||
2500⁄1 | 30 | 30 | 30 | 30 | 10 | 1 | |
3000⁄1 | 30 | 30 | 30 | 30 | 10 | 1 |