- Overzicht
- Aanbevolen producten
According to the different uses of the iron core, our company can produce various types of iron cores such as laminated iron cores, three-phase three-dimensional wound iron cores, and amorphous alloy iron cores.
Transformers are manufactured based on the principle of electromagnetic induction,and the magnetic circuit is the medium for electrical energy conversion.
The iron core is the main magnetic circuit of the transformer, and its main function is to conduct magnetism. It converts the electrical energy of the primary circuit into magnetic energy, and then converts the magnetic energy into the electrical energy of the secondary circuit.
At the same time, the iron core is also the mechanical skeleton of the transformer. The clamping device of the iron core not only makes the magnetic conductor a complete mechanical structure, but also has insulated coils sleeved on it, supports the leads, and installs almost all the internal components of the transformer.
The iron core has the largest weight among all the components of the transformer. It accounts for about 60% of the total weight in dry-type transformers and about 40% in oil-immersed transformers.
Typ een beschrijving
Prestatie parameter
Nr. | Testobjecten | Standaard vereisten | Actual data |
1 | Naad | ≤1.0mm | 1.0mm |
2 | Onbelast verlies | PO≤553W | 540W |
3 | Window diagonal | ≤2.0mm | 1.2mm |
4 | Isolatieweerstand | Iron core to ground insulation resistance 5MΩ | ≥5MΩ |
5 | steel | Verticalltys(2/1000)mm | s(2/1000)mm |
Curvatures(1.5/1000)mm | s(1.5/1000)mm | ||
6 | Lamination thickness | Main stage:60±1mm | 60mm |
Total stack thickness: 260±1mm | 260mm | ||
7 | Window height and width | Window height:317±1mm | 317mm |
Window width:185±1mm | 185mm | ||
8 | Clamp sizo Strictly implemented in accordance with the technical agreement,non-standardclamps implemented in accordance with the national standard dimensionaltolerance (C-level roughness) | Geslaagd | |
9 | Laminated wood:32.5±0.5mmFoot insulation 32.5±0.5mmPressboard:6±0.5mm6±0.5mm | 32.5mm | |
6mm | |||
10 | Standard part siz0 Strictly implemented in accordance with the technical agreement,non-standardparts implemented in accordance with the national standard dimensionaltolerance (C-level roughness) | Geslaagd | |
11 | Algemeen voorkomen | Strictly implemented in accordance with the technical agreement,non-standard implemented in accordance with the national standard dimensionaltolerance(C-level roughness) | Geslaagd |