All Categories
zw32-0

Medium Voltage Circuit Breakers

Home >  Products >  Circuit Breakers >  Medium Voltage Circuit Breakers

ZW32 Medium Voltage Circuit Breaker

  • Overview
  • Recommended Products

The ZW32-12 outdoor high-voltage vacuum circuit breaker is an outdoor power distribution switching device with rated voltages of 12kV, 24kV, 40.5kV and a three-phase alternating current of 50Hz or 60Hz.

The circuit breaker is mainly used for breaking and closing the load current, overload current,and shor-circuit current in the power line.

It has the functions of overload and short-circuit protection.

It meets the requirements of control and measurement.

It can also realize the functions of remote control and monitoring.

It is widely applied in the power distribution systems of substations, industrial and mining enterprises for control and operation purposes.

It is especially suitable for places where frequent operations are required.

 

Enforce standars

 

GB1984-2003 High voltage AC circuit breaker

DL/T402-2007 High voltage AC circuit breaker ordering technical conditions

IEC60056 High voltage AC circuit breaker

 

Type description

 

1.jpg

 

Normal service condition

 

Ambient temperature:-40℃ to+40℃;

Altitude: 2000m and below.

The surrounding air can be polluted by dust, smoke, corrosive gases, vapors, or salt mist,and the pollution level is Class III.

The wind speed does not exceed 34m/s (equivalent to 700Pa on the surface of a cylinder).

Special service conditions: The circuit breaker can be used under service conditions different from the normal ones specified above. For special requirements, please negotiate with us.

Special service conditions: The circuit breaker can be used under service conditions different from the normal ones specified above. For special requirements, please negotiate with us.

 

Performance parameter

 

Serialnumber name unit data
1 Rated voltage kV 12
2 Rated current A 630 1250
3 Rated frequency Hz 50
4 Rated insulationlevel 1min power frequencywithstand voliage Dry test 42/48(fracture)
Wet test kV 34
Secondary loopto ground 2
Lightning impulse withstand voltage (peak) 75/85(fracture)
5 Rated short circuit closing current (peak) kA 50 63
6 Rated short-time withstand current kA 20 25
7 Rated peak withstand current kA 50 63
8 Rated short circuit breaking current breaking times time 30
9 Rated short ircuit duration S 4
10 Rated operating voltage and rated voltage of auxiliary circult V DC220, AC220,AC/DC220
11 Rated operating sequence points-0.3s-Combine and-180s-Combine and
12 Overcurrent Tripping rated current A 5
13 Mechanical life time 10000
14 Allowable wear accumulation thickness of static and static contacts mm 3
15 Overcurrent Rated current of the trip device A 5
16 Current ratio of current transformer 200/5400/5600/5
17 Contact opening distance mm 9±1
18 Contact overreach mm 2±0.5
19 Average opening speed m/s 1.2±0.3
20 Average closing speed m/s 0.6±0.2
21 Opening time ms 20~40
22 Closing time ms 30~60
23 Closing bounce time ms ≤2
24 Tripole combination and switching are different ≤2
25 Phase loop DC resistance μΩ ≤80(Tape isolation≤150)

2.jpg

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000
inquiry

Get a Free Quote

Our representative will contact you soon.
Email
Name
Mobile/WhatsApp
Company Name
Message
0/1000