- Overview
- Recommended Products
Enforce standards
GB/T 20840《Transformer》
IEC 61869《Instrument transformers》
Type description
Normal service condition
Power factor:COSΦ=0.8 (lagging)
Rated secondary voltage: 100/3, 100/3
Rated frequency: 50Hz or 60Hz
Anti-fouling level: Grade II
Ambient temperature: The lowest temperature is -5℃, the highest temperature is +40℃,and the average daily temperature does not exceed 30℃
Altitude: ≤ 1000 meters
Performance parameter
Rated voltage ratio (V) | Rated insulation level (kV) | Accuracy level and rated Secondary Output (VA) | Limit output (VA) | Primary fuse | Weight (kg) |
3000/ V3/100/ V3/100 | 3.6/23/40 | 0.2/6P(3P)-3X30/1000.5/6P(3P)-3X60/1001/6P(3P)-3X100/1003/6P(3P)-3X200/100 | 3X600 | 0.5 | 155 |
6000/ V3/100/ V3/100 | 7.2/32/60 | ||||
10000/ V3/100/ V3/100 | 12/42/75 | ||||
6000/ V3/100/ V3/100/ V3/100 | 7.2/32/60 | 0.2/0.2/6P(3P)-3X15/3X15/1000.2/0.5/6P(3P)-3X15/3X15/1000.5/0.5/6P(3P)-3X30/3X30/100 | 0.5 | ||
10000/ V3/100/ V3/100/ V3/100 | 12/42/75 |